Description
Product Overview
The ATE8 series timers are designed for straightforward configuration and operation with an analog dial. These timers offer a wide variety of time ranges and output options, catering to different applications. The standard DIN size of W 48 x H 48 mm ensures easy and convenient installation, making them a versatile choice for various industrial settings.
Key Features
- DIN Standard Size: Compact dimensions of W 48 × H 48 mm for ease of installation in standard panels.
- User-Friendly Design: Simple and intuitive time setting with an analog dial, allowing for quick adjustments.
- Cost-Effective: Economical solution without compromising on essential features.
- Wide Time Range Options: Multiple time ranges available to suit different operational requirements.
- Versatile Power Supply: Compatible with both 100 - 240 VAC and 24 - 240 VDC, accommodating various power setups.
- Durable Construction: Built to withstand tough industrial environments, with high vibration and shock resistance.
Unit Descriptions
The front panel of the ATE8 Series timers includes the following components:
- Output Indicator (Red): Displays the status of the output relay.
- Power Indicator (White): Illuminates when powered on, with a flashing mode to indicate time progression.
- Time Range Setting Switch: Allows selection of time ranges, with options for seconds, minutes, and hours.
- Time Range Display: Clearly shows the selected time range.
- Time Setting Dial: Used to precisely adjust the timing within the selected range.
Accessories (Sold Separately)
- Bracket BK-S: Mounting accessory for easy installation.
- 8-pin Sockets: PG-08, PS-08(N) for secure and reliable connections.
Specifications
- DIN Size: W 48 x H 48 mm
- Power Supply: 100 - 240 VAC, 24 - 240 VDC
- Time Range: 1 sec to 24 hours (depending on model)
- Output: Relay, SPDT, DPDT options
- Contact Capacity: 250 VAC, 3A / 30 VDC, 3A
- Protection Rating: IP40
Ordering Information
The ATE8 Series offers various model configurations to meet specific timing needs:
- Max. Time Range Options:
- 1: 1 sec / 10 sec / 1 min / 10 min / 1 hour
- 3: 3 sec / 30 sec / 3 min / 30 min / 3 hour
- 6: 6 sec / 60 sec / 6 min / 60 min / 6 hour
- C: 12 sec / 12 min / 24 min / 12 hour / 24 hour
- Output Configurations:
- No mark: Time limit 1c + Instantaneous 1a
- D: Time limit 2c
- E: Time limit 1c + Instantaneous 1c
Documents
Can't find the information you need? Our datasheets have all the details. Access them here:
Additional Information
Model Variants: |
ATE8-4â–¡, ATE8-4â–¡D, ATE8-4â–¡E |
Function: |
Power ON Delay |
Return Time: |
≤ 200 ms |
Control Output: |
Relay |
Contact Type: |
ATE8-4â–¡: Time limit SPDT (1c) + Instantaneous SPST (1a) ATE8-4â–¡D: Time limit DPDT (2c) ATE8-4â–¡E: Time limit SPDT (1c) + Instantaneous SPDT (1c) |
Contact Capacity: |
250 VAC, 3A or 30 VDC, 3A resistive load |
Repeat Error: |
≤ ± 0.3% ± 10 ms |
SET Error: |
≤ ± 10% ± 50 ms |
Voltage Error: |
≤ ± 0.5% ± 10 ms |
Temperature Error: |
≤ ± 2% ± 10 ms |
Power Supply: |
100 - 240 VAC ±10%, 50/60 Hz, or 24 - 240 VDC ±10% |
Power Consumption: |
AC ≤ 3.5 VA, DC ≤ 2 W |
Insulation Resistance: |
≥ 100 MΩ (500 VDC megger) |
Dielectric Strength: |
2,000 VAC at 50/60 Hz for 1 minute |
Noise Immunity: |
± 2kV square-wave noise by noise simulator (pulse width 1 ㎲) |
Vibration Resistance: |
0.75 mm double amplitude at 10 to 55 Hz for 1 hour (operational) |
Shock Resistance: |
300 m/s² (≈ 30 G) operational, 100 m/s² (≈ 10 G) malfunction |
Relay Life Cycle: |
Mechanical: ≥ 5,000,000 operations; Electrical: ≥ 100,000 operations at 250 VAC, 3A resistive load |
Humidity Range: |
35 to 85%RH (operating and storage) |
Protection Rating: |
IP40 (front part, IEC standard) |