null
Autonics

High Performance Sensor Controllers PA10 Series

(No reviews yet) Write a Review
SKU:
PA10 Series
MPN:
PA10
Weight:
160.00 Grams
+971 4 259 5133

Description

Product Overview

The PA10 series sensor controllers deliver exceptional control capabilities with a variety of operation modes to suit diverse application needs. These controllers are designed for high-speed output response and can be easily installed using either a DIN rail or panel mount, offering flexibility and convenience. Available in three distinct models—general-purpose, 2-channel, and high-performance—the PA10 series is tailored to meet the specific demands of different environments and tasks.


Key Features

  • High-Speed Output Response: The PA10 series ensures fast and reliable performance, making it ideal for applications where timing is critical.
  • Flexible Installation Options: Mount the controller on a DIN rail or a panel, depending on your setup needs.
  • Multiple Model Options:
    • PA10-V: General-purpose controller suited for a wide range of applications.
    • PA10-W: 2-channel controller, perfect for managing dual inputs.
    • PA10-U: High-performance controller featuring 13 operation modes, including a flip-flop mode for level control and a timer operation mode.
  • Wide Range Power Supply: Compatible with a 100-240 VAC power supply, operating at 50/60 Hz, allowing for broad usage across different regions and setups.
  • Durable and Reliable: With a mechanical relay life cycle of at least 10,000,000 operations and an electrical life cycle of at least 100,000 operations, the PA10 series is built to last.

Product Models and Applications

PA10-V: General-Purpose Controller

The PA10-V model is designed for general applications, offering a straightforward and reliable solution for basic sensor control needs.

PA10-W: 2-Channel Controller

The PA10-W is perfect for situations where dual input channels are necessary, providing individual input logic for each channel.

PA10-U: High-Performance Controller

For more complex applications, the PA10-U model delivers advanced functionality with 13 configurable operation modes, including specialized modes for level control and timed operations.


Installation and Setup

DIN Rail Mounting

The PA10 series controllers are designed for easy installation on a DIN rail, making them compatible with a wide range of industrial environments.

Panel Mounting

Alternatively, the controllers can be panel-mounted, allowing for a clean and integrated setup in control panels and other enclosures.


Unit Descriptions and Controls

Indicators and Switches

  • Power Indicator: Displays the operational status of the controller.
  • Output Indicators (1/2): Show the status of the outputs.
  • Sensor Input Indicators (1/2): Illuminate when the sensor input signal is low.
  • Input Logic Switch: Allows selection between AND/OR logic.
  • Sensor Input Signal Switch: Configures the validity of input signals (NORM/INV).
  • IN 2 AND Logic Operation Switch: Controls reverse turn function or derivative action for input signal 2.
  • Operation Mode Setting Switch: Configures the controller to one of the 13 available operation modes (PA10-U model).
  • Timer/Frequency Selection Switch: Used for setting timers and frequencies depending on the operation mode.
  • Timer Time Setting Volume: Adjusts the timer settings.

Ordering Information

When ordering, refer to the product code structure to ensure you select the appropriate model for your needs:

  • PA10-V: General-purpose model.
  • PA10-W: 2-channel model.
  • PA10-U: High-function model with advanced features.

Documents

Can't find the information you need? Our datasheets have all the details. Access them here:

View AllClose

Additional Information

Power Supply:
100-240 VAC, 50/60 Hz
Power Consumption:
≤ 10 VA
Sensor Supply Power:
12 VDC ± 10%, approximately 200 mA
Input Logic:
AND/OR for PA10-U, AND for PA10-V, Individual for PA10-W
Input Method:
NPN/PNP, no-voltage or voltage input options
Output Response Time:
≤ 10 ms for relay, ≤ 0.05 ms for transistor
Relay Life Cycle:
Mechanical: ≥ 10,000,000 operations; Electrical: ≥ 100,000 operations
Dielectric Strength:
2000 VAC for 1 minute
Insulation Resistance:
≥ 100 MΩ at 500 VDC
Operating Temperature:
-10 to 55°C
Operating Humidity:
35-85% RH
Unit Weight:
PA10-U: ~150 g, PA10-V/W: ~160 g