null
Endress+Hauser

Compact Ultrasonic Level Transmitter Prosonic FMU30

(No reviews yet) Write a Review
SKU:
Compact Ultrasonic Level Transmitter Prosonic FMU30 series
Weight:
0.00 Grams
Call us: +971 4 259 5133

Description

Application

The Prosonic FMU30 ultrasonic level transmitter is suitable for a wide range of applications, including level monitoring in sewage treatment facilities, process water tanks, and in loading, storage, and buffer tanks. Its ultrasonic sensor utilizes advanced software algorithms, and all warning and alarm messages are displayed on the easy-to-read four-line text screen, enabling quick problem resolution. Additionally, the envelope curve can be visualized on the display, allowing for on-site analysis and precise error diagnostics.

This two-wire device provides continuous, non-contact level and flow measurement.

Process connection: Thread
Temperature range: -20 to +60°C (-4 to +140°F)
Pressure range: +0.7 to +3 bar (10 to 44 psi)
Maximum measuring distance:

  • Sensor 1½": Up to 5m (16ft) for liquids, and up to 2m (6.6ft) for bulk solids
  • Sensor 2": Up to 8m (26ft) for liquids, and up to 3.5m (11ft) for bulk solids

Blocking distance:

  • Sensor 1½": 0.25m (0.8ft)
  • Sensor 2": 0.35m (1.15ft)

Certifications: International explosion protection certificates

 


 

Benefits

  • Fast and easy commissioning through menu-guided, on-site operation with a four-line text display, available in 7 languages
  • On-site envelope curve display simplifies diagnostics
  • Linearization function (up to 32 points) allows for conversion of measured values into units of length, volume, or flow
  • Non-contact measurement minimizes maintenance requirements
  • Installation options starting from G 1½ or 1½ NPT threads
  • Integrated temperature sensor provides automatic compensation for temperature-related sound velocity variations

 

SPECIFICATIONS

Pressure Specifications

Measuring principle Ultrasonic
Characteristic / Application Compact ultrasonic transmitter
Supply / Communication 2-wire
Accuracy +/- 3 mm or +/- 0,2 % of set measuring range
Ambient temperature

-20 °C ... 60 °C

(-4 °F ... 140 °F)

Process temperature

-20 °C ... 60 °C

(- 4°F ... 140 °F)

Process pressure / max. overpressure limit

0.7 bar ... 3 bar abs

(10 psi ... 44 psi)

Main wetted parts PP/EPDM
Process connection

G / NPT 1 1/2"

G / NPT 2"

Blocking distance

1 1/2": 0.25 m (0.8 ft)

2":0.35 m (1.15 ft)

Application Application
Max. measurement distance Max. measurement distance
Communication

4...20 mA

Certificates / Approvals ATEX, CSA C/US, IEC Ex, NEPSI
Options

Accessory Enclosed:

UNI flange 2" ... 4"

Application limits Application limits

 Continuous / Solids Specifications

Measuring principle  Ultrasonic
 Characteristic / Application  Compact ultrasonic transmitter
 Supply / Communication  2-wire
 Accuracy  +/- 3 mm or +/- 0.2 % of set measuring range
 Ambient temperature  -20 °C ... 60 °C

(-4 °F ... 140 °F)

 Process temperature  -20 °C ... 60 °C

(-4 °F ... 140 °F)

 Process pressure / max. overpressure limit  0.7 bar ... 3 bar abs

(10 psi ... 44 psi)

 Main wetted parts  PP/EPDM
 Process connection  G / NPT 1 1/2"

G / NPT 2"

 Blocking distance  Sensor 1 1/2": 0.25 m

Sensor 2": 0.35 m

 Max. measurement distance  Sensor 1-1/2": 2 m (6.6 ft)

Sensor 2": 3.5 m (11 ft)

 Communication  4...20 mA
 Certificates / Approvals  ATEX, CSA C/US, IEC Ex, NEPSI
 Options  Accessory Enclosed:

UNI flange 2" ... 4"

 Application limits  Take notice of range diagram

 Point Level / Liquids Specifications

Measuring principle Ultrasonic Limit
Characteristic / Application Compact ultrasonic transmitter
Supply / Communication 2-wire
Ambient temperature

-20 °C...+60 °C

(-4 °F...+140 °F)

Process temperature

-20 °C...+60 °C

(-4 °F...+140 °F)

Process pressure / max. overpressure limit

0.7 bar...3 bar abs

(10 psi ...44 psi)

Main wetted parts PP/EPDM
Process connection

G / NPT 1 1/2"

G / NPT 2"

Blocking distance

Sensor 1 1/2": 0.25 m,

Sensor 2": 0.35 m

Communication 4...20 mA
Certificates / Approvals ATEX, CSA C/US, IEC Ex, NEPSI
Options

Accessory Enclosed:

UNI flange 2"... 4"

Application limits Take notice of range diagram

Point Level / Solids Specifications

 

Measuring principle Ultrasonic Limit
Characteristic / Application Compact ultrasonic transmitter
Supply / Communication 2-wire
Ambient temperature

-20 °C...+60 °C,

(-4 °F...+140 °F)

Process temperature

-20 °C...+60 °C,

(-4 °F...+140 °F)

Process pressure / max. overpressure limit

0.7 bar...3 bar abs,

(10 psi ...44 psi)

Main wetted parts PP/ EPDM
Process connection

G / NPT 1 1/2",

G / NPT 2"

Blocking distance

Sensor 1 1/2": 0.25 m,

Sensor 2": 0.35 m

Communication 4...20 mA
Certificates / Approvals ATEX, CSA C/US, IEC Ex, NEPSI
Options

Accessory Enclosed:

UNI flange 2"...4"

 Application limits  Take notice of range diagramm

 

Documents

You may want to read this product's catalog. If so, please click to view the Endress+Hauser Ultrasonic measurement Time of Flight Prosonic FMU30 Series datasheet.
View AllClose