null
Datexel

Head Mount Temperature Transmitter with Thermocouple Input, Voltage Output - DAT 1135

(No reviews yet) Write a Review
SKU:
DAT 1135
MPN:
DAT1135
Weight:
50.00 Grams
Minimum Purchase:
1 unit

Description

Datexel Isolated converter with Output 0-10 V programmable by PC -  DAT 1135

Multiple temperature Input, highly Accurate, Current Output, Made in Italy

 

The isolated converter DAT1135 is able to execute many functions such as: measure and linearisation of the temperature characteristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected on its input.

The DAT1135 is able to measure and linearise the standard thermocouples with internal cold junction compensation. The measured values are converted in a 0-10 V signal. The device guarantees high accuracy and performances stability both in time and in temperature.

The programming of the DAT1135 is made by a Personal Computer using the software DATESOFT, developed by DATEXEL, that runs under the operative system "WindowsTM ". By use of DATESOFT, it is possible to configure the device in order to interface it with the most used sensors.

For Resistance and RTDs sensors it is possible to program the cable compensation with 3 or 4 wires; for Thermocouples it is possible to program the Cold Junction Compensation (CJC) as internal or external.

It is possible to set the minimum and maximum values of input and output ranges in any point of the scale, keeping the minimum span shown in the table below.

It is available the option of alarm for signal interruption (burn-out) that allows to set the output value as high or low out of scale.

On the device is provided a function that allows the user to set a programmable filter up to 30 seconds to reduce eventual sudden variations of the input signal.

The programming of the device can be executed without the power supply connected using the interface PRODAT05 or PRODAT06.

The 1500 Vac isolation between input and power supply/output eliminates the effects of all ground loops eventually existing and allows the use of the converter in heavy environmental conditions found in industrial applications.

It is housed in a self-extinguish plastic enclosure suitable for DIN B in-head mounting.

Moreover ( by proper mounting kit ) it is possible to mount the DAT1135 on DIN rail.

The advantages for DAT1135:

  • Configurable input for RTD, TC, mV, Resistance and Potentiometer
  • Galvanic isolation at 1500 Vac
  • Voltage output configurable from 0 up to 10 Vdc
  • Configurable by Personal Computer
  • Configurable by interface PRODAT05 or PRODAT06 without power supply connected
  • High accuracy
  • On-field reconfigurable
  • EMC compliant – CE mark
  • Suitable for DIN B in-head mounting
  • Option for DIN rail mounting in compliance with EN 50022 (DIN RAIL Option)

Input for DAT1135 Converter is:

  • Thermocouple (*) CJC int./ext.

J -200°C 1200°C 100°C

K -200°C 1300°C 100°C

S 0°C 1750°C 400°C

R 0°C 1750°C 400°C

B 0°C 1800°C 400°C

E -200°C 1000°C 100°C

T -200°C 400°C 100°C

N -200°C 1300°C 100°C

  • RTD (*) 2,3,4 wires

Pt100 -200°C 850°C 50°C

Pt1000 -200°C 185°C 30°C

Ni100 -60°C 180°C 50°C

Ni1000 -60°C 150°C 30°C

  • Voltage

mV -100mV +90mV 5 mV

mV -100mV +200mV 10 mV

mV -100mV +800mV 20 mV

  • Potentiometer

(R nom. < 50 KW) 0% 100% 5%

  • RES. 2,3,4 wires

0 W 500 W 50 W

0 W 2000 W 500 W

Output for DAT1135 Converter is:

  • Direct voltage 0 V 10 V 1 V
  • Reverse voltage 10 V 0 V 1 V

Response time

  • Response time (10- 90%) about 200 ms

Power supply

  • Power supply voltage is 18 .. 30 Vdc and the Reverse polarity protection is equal to 60 Vdc max.

Temperature & humidity

  • Operative temperature -40°C .. +85°C
  • Storage temperature -40°C .. +85°C
  • Humidity (not condensed) 0 .. 90 %

Industries/applications

  • Furnace
  • Oil and gas
  • Brick manufacturing
  • Heat Exchangers
  • Industrial Processes
  • Heating/cooling systems

Series Information

"DAT1000 SERIES": temperature transmitters for DIN B in-head mounting

The transmitters of the DAT1000 series can accept at their input signals coming from 2,3 or 4 wires Pt100, thermocouple and potentiometer sensors or voltage signals (mV).The devices provide a 4-20 mA two wire current loop output signal.
The series is composed of devices with input configurable by PC with or without galvanic isolation. Moreover, it is available a version of the transmitters of the DAT1000 series developed for the use in potentially explosive atmospheres certified in according to the DIRECTIVE ATEX 94/9/EC. (see p. 24 to 26).

  • DAT 1010: Two wire transmitter for RTD programmable by PC
  • DAT 1015Two wire universal transmitter programmable by PC
  • DAT 1061: Isolated two wire Transmitter for RTD programmable by PC
  • DAT 1066: Isolated two wire universal transmitter programmable by PC

About Datexel:

Founded in 1992 from the commitment and aspiration of several partners as a small provincial company, through the years DATEXEL has become an established reality on Italian and international markets as a manufacturer of electronic equipment for industrial automation and control process.

The range of DATEXEL products includes:  Transmitters, signal and temperature Converters (both analogue and digital), galvanic Isolators, signal Splitters, I/O Modules, Trip Amplifiers, Power Supply Units, current loop Isolators, analogue and digital Displays.

Datexel Products are used in following industries:

  • Steel production
  • Automotive
  • Oil and gas
  • Shipbuilding

Documents

You may want to read this product's catalog. If so, please click to view the DAT1135 datasheet.
View AllClose

Warranty Information

One Year Warranty.
View AllClose

Additional Information

Input signal type:
RTD, Potentiometer, Voltage, Resistance.
Input calibration:
RTD > of ±0.1% f.s. or ±0.2°C. Low res. > of ±0.1% f.s. or ±0.15 Ω. High res. > of ±0.2% f.s. or ±1 Ω. TC, mV > of ±0.1% f.s. or ±10 uV.
Input impedance:
mV >= 10 MΩ.
Output type Direct Voltage:
Min. 0V. Max. 10V.
Output type Reverse Voltage:
Min. 10V. Max. 0V.
Output calibration:
Voltage ± 5 mV.
Output load resistance:
Voltage output ≥ 5 KΩ. Short-circuit current 26 mA max.
Output filter programmability:
Selectable from 0.2 to 30 s.
Linearity:
TC ± 0.2 % f.s. RTD ± 0.1 % f.s.
Line resistance influence:
TC, mV <=0.8 uV/Ohm. RTD 3 wires 0.05%/Ω (50Ω balanced max.). RTD 4 wires 0.005%/ Ω (100Ω balanced max.).
RTD excitation current:
Typical 0.350 mA.
CJC comp.:
± 0.5°C.
Thermal drift:
Full scale ± 0.01% / °C. CJC ± 0.01% / °C.
Burnout values:
Max. Fault value about 11.1 V. Min. Fault value about -0.65 V.
Response time (10÷ 90%):
About 200 ms.
Power supply:
Power supply voltage 18 …30 Vdc. Current consumption 10 mA max. Reverse polarity protection 60 Vdc max.
Isolation voltage:
Input – Pow. supply/Output 1500 Vac, 50 Hz,1min.
Temp. and humidity:
Operative temperature -40°C …+85°C. Storage temperature -40°C …+85°C. Humidity (not condensed) 0 …90 %.
Housing:
Material PC + ABS V0. Mounting DIN B head or bigger. Weight about 50 g. Dimensions Ø= 43 mm ; H = 24 mm
EMC (for industrial environments):
Immunity EN 61000-6-2. Emission EN 61000-6-4.
View AllClose