null
Datexel

Potentiometer Converter Analog Output - DAT205 3W

(No reviews yet) Write a Review
SKU:
DAT205 3W
MPN:
DAT205 3W
Weight:
50.00 Grams
Minimum Purchase:
1 unit

Description

Datexel Potentiometer Converter Analog Output - DAT205 3W

High Accuracy, Linearized Output, Italian Made

The converter DAT 205 3W is designed to provide on output a linearized voltage or current signal proportional with the variation of resistance introduced from the potentiometer connected to its input; to make the measure, a 1 Vdc voltage reference is provided at the ends of the potentiometer.

The regulations of the zero and full-scale value are made using the ZERO and SPAN potentiometers; there is not influence between the regulations.

The command SEL must be used to enable or disable the output of the device in the case in which will be necessary to connect more than one DAT 205 3W to only one A/D input.

It is housed in a plastic enclosure of 17 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.

The advantages for DAT205 3W:

  • Input for potentiometer
  • Zero and Span values adjustable by potentiometers
  • Linearised output in voltage or current
  • Command SEL for enable / disable output
  • High accuracy
  • EMC compliant – CE mark
  • Suitable for DIN rail mounting in compliance with EN 50022 and EN-50035

Input for DAT205 3W

  • Sensor type: Potentiometer
  • Potentiometer's resistance: Minimum nominal value = 1 KW; Maximum nominal value = 10 KW.
  • Voltage reference: 1Vdc

Output for DAT205 3W

  • Output type: 4 ÷ 20 mA, 0÷20 mA or 0÷10 V
  • Maximum output signal: 15 V or 25 mA
  • Load resistance (Rload): Current output: ≤ 500 W; Voltage output: ≥ 2 KW

SEL command

SEL Command for DAT205 3W is like bellow:

  • Disable output: 5 ÷ 30 Vdc
  • Enable output: 0 Vdc or not connected

Performances

Calibration, linearity, response time and other factor related to performance is as follows:
  • Calibration error: ± 0.1 % of f.s.
  • Linearity error: (*) ± 0.1 % of f.s.
  • Thermal drift: 0.02 % of f.s./°C
  • Response time: (from 10 to 90 % of f.s.) 500 ms
  • Power supply voltage: (**) 18÷30 Vdc
  • Current consumption: Current output: 30 mA max. Voltage output: 10 mA max.

Electromagnetic Compatibility (EMC)

  • (for industrial environment) Immunity: EN 61000-6-2; Emission : EN 61000-6-4
  • Operating temperature: -20 ÷ 70 °C
  • Storage temperature: - 40 ÷ 85 °C
  • Relative humidity: (non cond.) 0 ÷ 90%
  • Maximum Altitude: 2000 m
  • Installation: Indoor
  • Category of installation: II
  • Pollution: Degree 2
  • Weight: approx. 50 g

Mechanical Specifications

The type of material, the protection type and other matter related to DAT205 3W mechanical specs is as follows:
  • Material: Self-extinguish plastic
  • IP Code: IP20
  • Wiring: wires with diameter 0.8÷2.1 mm2 /AWG 14-18
  • Tightening Torque: 0.8 N m
  • Mounting: in compliance with DIN rail standard EN-50022 and EN-50035

Industries/applications

  • Furnace
  • Oil and gas
  • Brick manufacturing
  • Heat Exchangers
  • Industrial Processes
  • Heating/cooling systems

Series Information

“DAT200, DAT500 SERIES”: signal transmitters and converters, galvanic isolators

The transmitters and converters of the DAT200 series can accept on their input signal coming from potentiometer sensors (DAT205) or voltage and current signals (DAT207) The series is composed of:

Not isolated transmitter for potentiometer input from 1 Kohm up to 10 Kohm. Powered from 4÷20 mA current loop (DAT205 2W).

Not isolated converter for potentiometer input from 1 Kohm up to 10 Kohm. Fixed range (DAT205 3W).

Not isolated transmitter for mV, V, mA input. Fixed range. Powered from 4÷20 mA current loop (DAT207 2W).

Not isolated converter for mV, V, mA input. Fixed range. (DAT207 3W).

Self-powered, 3000 Vac isolated converter for 0÷20 mA current loop. (DAT511).

Self-powered, 1500 Vac isolated converter for 0÷20 mA current loop. Hart compatible (DAT511-H)

About Datexel:

Founded in 1992 from the commitment and aspiration of several partners as a small provincial company, through the years DATEXEL has become an established reality on Italian and international markets as a manufacturer of electronic equipment for industrial automation and control process.

The range of DATEXEL products includes: Transmitters, signal and temperature Converters (both analogue and digital), galvanic Isolators, signal Splitters, I/O Modules, Trip Amplifiers, Power Supply Units, current loop Isolators, analogue and digital Displays.

Documents

To View Data Sheet for Datexel Potentiometer Converter Analog Output DAT205 3W Please Click Here
View AllClose

Warranty Information

One Year Warranty.
View AllClose

Additional Information

Sensor type:
Potentiometer.
Potentiometer's resistance:
Min. nominal value = 1 KΩ; Max. nominal value = 10 KΩ
Voltage reference:
1Vdc.
Output type:
4 ÷ 20 mA, 0÷20 mA or 0÷10 V.
Maximum output signal:
15 V or 25 mA.
Load resistance (R-load):
Current output: ≤ 500 Ω; Voltage output: ≥ 2 KΩ.
Disable input:
5 ÷ 30 Vdc.
Enable output:
0 Vdc or not connected.
Calibration error:
± 0.1 % of f.s.
Linearity error (*):
± 1 % of f.s.
Thermal drift:
0.02 % of f.s./°C.
Response time (from 10 to 90 % of f.s.):
500 ms.
Power supply voltage (**):
18÷30 Vdc.
Current consumption(***):
Current output: 30 mA max. Voltage output: 10 mA max.
Electromagnetic Compatibility (EMC for industrial environment ):
Immunity: EN 61000-6-2; Emission: EN 61000-6-4.
Operating temperature:
-20 ÷ 70 °C.
Storage temperature:
- 40 ÷ 85 °C
Relative humidity (non cond.):
0 ÷ 90%.
Maximum Altitude:
2000 m.
Installation:
Indoor.
Category of installation:
II.
Pollution degree:
2.
Weight:
50g approx.
Material:
Self-extinguish plastic.
IP code:
IP20.
Wiring:
Wires with diameter 0.8÷2.1 mm2 /AWG 14-18.
Tightening torque:
0.8 Nm.
Mounting:
In compliance with DIN rail standard EN-50022 and EN-50035.
View AllClose