Danfoss
Pressure Switch SPDT, low pressure - KP1
- SKU:
- KP1
- Weight:
- 300.00 Grams
- Maximum Purchase:
- 3 units
Description
Danfoss pressure switch KP1
Low pressure, Male flare connection type, Climate solutions for cooling
KP1 pressure switches are for use in refrigeration and air conditioning systems to give protection against excessively low suction pressure or excessively high discharge pressure. This pressure switches are suitable foe oil-free applications and are not applicable for liquid line.
The switches are also used for starting and stopping refrigeration compressors and fans on air-cooled condensers. KP1 pressure switches are available in IP44 enclosures.
The KP1 pressure switch has several codes, representing different properties. Most popular ones are:
- 060-110166: with Auto reset and flare connection
- 060-110366: with manual reset and flare connection
As a quick report, this pressure switch provides:
- Ultimate installation protection against freezing
- Small dimensions
- Space-saving, easy to install
- Shock and impact resistant
- Ultra-short bounce time
Body
In KP1 pressure switches, parts that are in contact with the medium are made from Tin bronze and Nickel plated free cutting steel.
Enclosure IP44 is obtained when the units with top cover are mounted on a flat surface or bracket. The bracket must be fixed to the unit so that all unused holes are covered.
Reset function
These pressure switches feature both manual and auto reset functions. Units with manual reset can only be reset during operation by activation of the reset button. And in units with auto reset, the unit will reset automatically after operational stop. Each KP1 code have its own type of reset function. This function for the two common codes is:
- 060-110166: Auto reset
- 060-110366: Manual reset
Set up ranges
To set up your KP1 pressure switch, you can choose a value in regulating range. This value is your cut-in or start pressure. And by choosing the differential (Δp) value, you can build your cut-out or stop pressures. In this product and other low-pressure products, the cut-in pressure minus Δp will form the cut-out pressure. The regulating range and differential (Δp) differ from a KP1 code to another, as well. These values for the common codes are:
- 060-110166: Regulating range of -0.2 to 7.5 bar, and differential (Δp) range of 0.7 to 4.0 bar
- 060-110366: Regulating range of -0.9 to 7.0 bar, and differential (Δp) value of 0.7 bar
Low pressure switches with manual reset, can be manually reset when the pressure is equal to the stop pressure plus the differential.
Take notice that the stop pressure must be above absolute vacuum (Pe = -1 bar)! And also, max. working pressure of this product is 17 bar.
Pressure connection
Pressure connection of this pressure switch is different from one code to another. But the pressure connection for both 060-110166 and 060-110366 popular codes is male ¼ in. flare, with the DIN 8906 standard.
Electrical connection
The electrical connection of KP1 pressure switches is rubber cable gland, which can be used for cables with 6 to 14 mm diameter.
Design
Here is the schematic picture of KP1:
1. Low pressure (LP) setting spindle
2. Differential setting spindle, (LP)
3. Main arm
5. Main spring
6. Differential spring
7. Bellows
8. LP connection
9. Earth terminal
10. Terminals
11.Earth terminal
12. Cable entry
13. Tumbler
14. Locking plate
15. Reset button
Temperature
Different permissible temperature conditions are defined for using this product:
- Ambient temperature: -40 … 65°C
- Medium temperature: -50 … 100°C
Industries / applications
- Refrigeration
- Air conditioning systems
- Compressors
- Air-cooled condensers
Series Information
KP Series
Pressure switches for commercial refrigeration applications
Danfoss KP series pressure switches are specialized for use in refrigeration and air conditioning systems to make protection against excessively low suction pressure or excessively high discharge pressure. The switches are also used for starting and stopping refrigeration compressors and fans on air-cooled condensers.
With the KP pressure switches you get great reliability and long service life due to the snap-action function ensuring ultra-short bounce times. The KP pressure switch is available with IP30, IP44 and IP55 enclosures for appropriate protection based on the application.
KP series main features
• Ultimate installation protection against freezing
• Small dimensions
• Space-saving, easy to install
• Shock and impact resistant
• Ultra-short bounce time
Documents
Additional Information
Pressure range category: |
Low pressure |
Regulating range: |
-0.2 ... 7.5 bar / 0.7 ... 4.0 bar |
Differential (∆p): |
0.7 ... 4.0 bar / 0.7 bar |
Pressure sensing element: |
Bellows |
Contact Function: |
SPDT |
Reset: |
Auto / Manual (min.) |
Pressure connection: |
¼ in. 6 mm Flare / ¼ in. ODF solder / 6 mm ODF solder |
Electrical connection: |
Rubber cable gland |
Electrical connection size: |
6 ... 14 mm |
Enclosure rating IP: |
IP30 / IP44 / IP55 |
Max. Working Pressure: |
17 bar |
Ambient temperature: |
-40 ... 65 °C |
Media temperature: |
-50 ... 100 °C |