Pressure transmitter 63 bar, 4-20 mA, HART - SITRAN P320

(No reviews yet) Write a Review
SKU:
7MF0300-1TF02-5AF2-Z
UPC:
7MF0300-1TF02-5AF2-Z
Weight:
3,300.00 Grams
  • SIEMENS SITRANS P320
  • SIEMENS SITRANS P320 - Information tag
  • SITRANS P320 Series
  • SIEMENS SITRANS P320 - Back
  • SIEMENS SITRANS P320 and its spare parts
  • SIEMENS SITRANS P320 - Side

Description

SIEMENS Pressure Transmitter 4-20 mA & HART, 63 bar - 7MF0300-1TF02-5AF2-Z

Adjustable Pressure Range, 0.065% FS accuracy, Stainless steel 316L

 

Ensure unparalleled precision and reliability in your pressure measurement with this product from Siemens SITRANS P320 series. This versatile pressure transmitter boasts exceptional accuracy, robust construction, and user-friendly features, empowering you to optimize process control and achieve peak performance.

Body

We understand how crucial a transmitter's body is for long-term performance. That's why the SITRANS P320 is built to endure even the toughest conditions. The core components are constructed from high-grade stainless steel (316L and CF3M), renowned for their exceptional resistance to corrosion and wear. This ensures reliable pressure measurement for years to come, even in harsh environments with extreme temperatures or chemical exposure.

The separation membrane, also crafted from 316L stainless steel, provides a robust barrier between the process medium and the internal measuring cell.

We haven't overlooked the finer details either. The gasket between the sensor and housing is made from NBR, a resilient material that provides a tight seal and prevents leaks. The filling liquid within the measuring cell is silicone oil, chosen for its stability and ability to transmit pressure effectively across a wide temperature range.

Finally, the multi-segment display with four pushbuttons offers clear visibility and easy operation, even in low-light conditions and with fluctuations in ambient temperature (-20°C to 80°C). The SITRANS P320 is built to endure, so you can focus on what matters most – optimizing your process.

Pressure Measuring Range

This product from the SITRANS P320 series is designed to handle a wide range of pressure applications. It covers a gauge pressure range of -0.97 to 63 bar, and within that range, you can conveniently adjust the measuring span to best suit your specific needs. This flexibility ensures you get the most accurate readings possible for your unique process.

For detailed instructions on adjusting the pressure range and units, please refer to the 'Pressure Range Adjustment' tab on this page.

Process Connection

This pressure transmitter features a standard 1/2"-14 NPT process connection for seamless integration into your existing piping system. This ensures easy installation and minimizes downtime during setup. No need to worry about complicated modifications – the P320 is designed to fit right in.

Electrical connection

This pressure transmitter from the SITRANS P320 series is built for user-friendly connections. It features two M20 x 1.5 screw-type terminals for the electrical connection. This industry-standard design allows for quick and secure wiring, minimizing installation time and ensuring a reliable connection. No need for special tools or complicated procedures – the P320 gets you up and running fast.

Output signal

This product offers unmatched versatility in communicating process data. It provides a standard 4-20 mA current output for seamless integration into existing control systems. But that's not all. It also supports the HART communication protocol (version 7), allowing for real-time access to critical data beyond just pressure. You can monitor vital details like electronic device temperature and measuring cell temperature, giving you a deeper understanding of your process health. With the ability to transmit up to four values simultaneously, the P320 empowers you to make data-driven decisions and optimize your operation for peak performance.

Accuracy

In any pressure measurement system, precision is paramount. That's why this pressure transmitter boasts an impressive relative accuracy of 0.065%, ensuring highly reliable readings you can trust. This exceptional accuracy is maintained even at a reference temperature of 25°C. Furthermore, the P320 adheres to the stringent IEC 62828-1 standard for measuring accuracy, giving you peace of mind that your measurements meet the highest industry expectations. With the SITRANS P320, you can be confident in the integrity of your data and make process decisions with absolute certainty.

Temperature

The SITRANS P320 is designed to perform reliably in a wide range of temperature environments:

  • Medium temperature: -40 °C to 100 °C - Handles harsh process conditions
  • Ambient temperature: -40 °C to 85 °C - Functions well in extreme heat or cold
  • Storage temperature: -50 °C to 85 °C - Withstands fluctuations during storage and transport
  • Transport temperature: -40 °C to 85 °C - Maintains integrity during transportation
  • Relative humidity during operation: 4 to 95% - Operates effectively in humid environments

You can be confident that the SITRANS P320 will deliver accurate readings regardless of the surrounding conditions.

 

Pressure Range Adjustment

Fine-Tune Your Pressure Measurement: A Guide to Configuring the SITRANS P320

The SITRANS P320 offers exceptional flexibility when it comes to pressure measurement. This tab equips you with the knowledge to:

  • Select the appropriate pressure unit for displaying readings based on your needs.
  • Calibrate the measuring range to perfectly align with your specific application, ensuring optimal performance and accurate data.

By following these user-friendly guides, you can effortlessly configure your SITRANS P320 for precise pressure measurement and achieve superior results in your process.

Configuring Pressure Units on the SITRANS P320: A User-Friendly Guide

The SITRANS P320 offers the flexibility to display pressure readings in various units, catering to your specific needs. Here's a simplified guide to navigate this process:

  1. Navigate to the parameter view.
  2. Select the "Pressure units" parameter.
  3. Press the â–¶ button.
  4. Select the desired unit with the â–² or â–¼ button. The pressure measurement is converted to the new pressure unit.
  5. Use the â–¶ button to confirm.
  6. Navigate to the "Pressure reference" parameter.
  7. Press the â–¶ button.
  8. Select the specific pressure unit for your application (absolute pressure, gauge pressure, none) with the â–² or â–¼ button.

Important Note: If the converted pressure measurement exceeds five digits after unit selection, the display will show "#####" to indicate overflow.

By following these simple steps, you can effortlessly configure the pressure unit on your SITRANS P320, ensuring that pressure readings are displayed in a format that aligns with your specific needs and application.

Calibrating Your SITRANS P320 for Precise Pressure Measurement

The SITRANS P320 empowers you to tailor its measuring range to perfectly suit your specific application. Here's a breakdown of the process, ensuring you achieve optimal performance:

Setting the Measuring Range (Without Applied Pressure):

  1. Navigate into the parameter view.
  2. In the parameter view, set the "Lower range value" parameter.
  3. Press the â–¶ button.
  4. Enter a value within the measuring limits with the â–² and â–¼ buttons.
  5. Use the â–¶ button to confirm.
    The lower range value is set. Note that the upper range value does not move automatically.
  6. Navigate to the "Set upper range value" parameter.
  7. Enter a value within the measuring limits with the â–² and â–¼ buttons.
  8. Press the â–¶ button.
  9. Set the lower range value with the â–² and â–¼ buttons.
  10. Use the â–¶ button to confirm.
    The upper range value is set.

Important Reminder: The SITRANS P320 safeguards against setting a measuring span (difference between upper and lower ranges) that's too small. If you attempt to do so, a "FAILD" message will appear. Ensure your chosen range provides sufficient resolution for your needs.

Applying the Measuring Range (With Pressure Present):

Now, let's assume your SITRANS P320 is already mounted with pressure applied:

  1. Navigate into the parameter view.
  2. Select the "Apply lower range value" parameter.
  3. Press â–¶ the button.
    The existing pressure is displayed.
  4. Use the â–¶ button to confirm.
    The wizard starts.
    The wizard ends with the "COMPL" message.
  5. Navigate to the "Apply upper range value" parameter.
    The existing pressure is displayed.
  6. Press the â–¶ button.
    The wizard starts.
    The wizard ends with the "COMPL" message.

Important Safety Note: The wizard will display a "FAILD" message if:

  • The applied pressure falls outside the measuring limits of the instrument.
  • The chosen measuring span is below the minimum permissible range for the sensor.

By following these steps, you can confidently configure the measuring range on your SITRANS P320, ensuring accurate pressure readings tailored to your specific process requirements. This level of control empowers you to optimize performance and achieve superior results.

Documents

Empower Your Knowledge: Essential Resources for the SITRANS P320

Dive deeper into the capabilities of your SITRANS P320 with our comprehensive library of resources. Here, you'll find everything you need to maximize its potential:

  • Operating Instructions: This detailed guide provides step-by-step instructions for operating and maintaining your SITRANS P320, ensuring you get the most out of your investment.
  • Configuration Result: Gain valuable insights into your specific device configuration with this document. It serves as a convenient reference for all your settings and parameters.
  • Datasheet: Explore the technical specifications and features of the SITRANS P320 in detail. This datasheet empowers you to fully understand the capabilities of your pressure transmitter.

By exploring these resources, you'll gain the knowledge and confidence to operate your SITR2ANS P320 effectively and achieve peak performance in your pressure measurement applications.

View AllClose

Additional Information

Reference Pressure:
Gauge
Measuring Range:
-0.97 … 63 bar
Measuring Span:
0 … 63 bar
Supply Voltage:
10.5 … 45 VDC
Current Output:
4 ... 20 mA
Communication Protocol:
HART
Electrical connections:
2 x M20 x 1.5
Process Connection:
1/2"-14 NPT
Process connection material:
Stainless Steel 316L / 1.4404
Enclosure Material:
stainless steel CF3M / 1.4409 (similar to 316L)
Separation & Measuring Membrane Material:
Stainless Steel 316L / 1.4404
Material of the Gasket Between Sensor and Housing:
acrylonitrile-butadiene-styrol-rubber (NBR)
Filling Liquid:
Silicone Oil
Measuring Accuracy:
0.065 %FS
Design of the Display:
Multisegment Display
Medium Temperature:
-40 … 100 °C
Ambient Temperature:
-40 … 85 °C
Storage Temperature:
-50 … 85 °C
Transport Temperature:
-40 … 85 °C
Relative Humidity During Operation:
4 … 95 %