Description
Product Overview
The DAT2105 3W Signal Converter is designed to transform voltage signals derived from a connected potentiometer into standardized current or voltage outputs. It provides consistent, high-precision measurements with exceptional stability over time and under varying temperature conditions. Customers must specify their desired output range when ordering, with options including 0-20mA, 4-20mA, 0-10V, or 0-5V.
Please note that the product photo may not accurately represent the actual item. Always refer to the datasheet during installation to ensure proper setup and compliance with safety standards.
General Description
The DAT2105 3W converter is a versatile tool for converting voltage signals from a potentiometer into normalized current or voltage signals. This high-precision device ensures stable measurements and features a front-mounted PWR LED to indicate the correct power supply status. Users can also opt for a sensor interruption alarm, which can be configured to indicate either a high or low overrange, depending on the needs of the application.
For systems requiring manual output signal adjustment, the "- POT" option equips the device with front-facing potentiometers. The device's compact design, housed in a 12.5 mm thick plastic case, supports DIN rail mounting in accordance with EN-50022 and EN-50035 standards.
User Instructions
To ensure proper operation, all power supply, output, and input connections should be made as outlined in the "Connections" section of the product manual. Proper installation and adherence to these guidelines will optimize the device's performance.
Technical Specifications
- Input Type: Potentiometer (nominal value < 50 kΩ), adjustable from 0% to 100%.
- Input Accuracy: ± 0.05% full scale.
- Thermal Drift: ± 0.01% per °C of full scale.
- Output Options: Current (0-20mA, 4-20mA) or Voltage (0-10V, 0-5V).
- Output Resolution: Current output accuracy is ± 7 µA, voltage output accuracy is ± 4 mV.
- Burn-out Values: Max output - 22 mA or 11V; Min output - 0 mA or -0.8V.
- Output Load Resistance: Current output < 500 Ω; Voltage output > 5 kΩ.
- Response Time: Approximately 220 ms (10% to 90% of the output range).
- Potentiometer Adjustment (Option "- POT"): Zero and Span adjustments are both ± 5%.
Environmental Conditions
- Operating Temperature: -20°C to +70°C.
- Storage Temperature: -40°C to +85°C.
- Humidity: 0% to 90%, non-condensing.
- Maximum Altitude: 2000 meters.
- Installation Category: II.
- Pollution Degree: 2.
- Usage: Indoor installation.
Mechanical Specifications
- Material: Self-extinguishing plastic for enhanced safety.
- IP Rating: IP20.
- Wiring Compatibility: Suitable for wire diameters from 0.8 to 2.1 mm² (AWG 14-18).
- Tightening Torque: 0.8 Nm for secure installation.
- Mounting: Complies with DIN rail standards EN-50022 and EN-50035.
- Weight: Approximately 90 grams.
Certifications
- EMC Compliance: Conforms to EN 61000-6-2 (Immunity) and EN 61000-6-4 (Emission) standards for industrial environments.
- UKCA Compliance: Meets BS EN 61000-6-2 and BS EN 61000-6-4 standards for immunity and emissions.
Installation Instructions
The DAT2105 3W should be mounted vertically on a DIN rail in locations free from vibrations to ensure optimal performance. It is advisable to avoid routing wiring near power signal cables to prevent interference.
Wiring Instructions
Correct input, power supply, and output connections are critical to the device's performance. The datasheet provides detailed guidance on the correct terminals for grounding, voltage output, and current output.
Light Signaling
- PWR LED: The green LED indicates the power status of the device. When lit, the device is powered on; when off, the device is not powered.
Recycling Instructions
This product should not be disposed of as household waste. It must be taken to an authorized recycling facility for electronic waste disposal. For more information, contact your local waste management services or the product supplier.
Ordering Information
When placing an order for the DAT2105 3W, please specify the desired output range and any additional options, such as the "- POT" potentiometer adjustment feature or burn-out alarm settings.
Documents
You may want to read this product's catalog. If so, please click to view the Datexel DAT2105 3W Series datasheet.Additional Information
Input Type: |
Potentiometer, < 50 kΩ |
Input Accuracy: |
± 0.05% full scale |
Thermal Drift: |
± 0.01% per °C |
Output Options: |
0-20mA, 4-20mA, 0-10V, 0-5V |
Output Resolution: |
Current ± 7 µA, Voltage ± 4 mV |
Burn-out Values: |
Max 22 mA or 11V, Min 0 mA or -0.8V |
Response Time: |
220 ms |
Storage Temperature: |
-40°C to +85°C |
Weight: |
90 g |
Mounting: |
DIN rail, EN-50022 and EN-50035 compliant |
Certifications: |
EN 61000-6-2, EN 61000-6-4, BS EN 61000-6-2, BS EN 61000-6-4 |