Datexel
Temperature Transmitter and Signal Converter Current, Voltage Output - DAT4235 IS/A
- SKU:
- DAT4235 ISA
- MPN:
- DAT4235ISA
- Weight:
- 500.00 Grams
- Minimum Purchase:
- 1 unit
Description
Datexel Temperature Transmitter and Signal Converter - DAT4235 IS/A
Current and Voltage Input, Thermocouple Input, Current and voltage Output
The input measures mV, V, mA or resistance signals, and can be directly connected to Thermocouple, RTD or potentiometer sensors.
The input signal is filtered, linearised, amplified and transferred to the output circuit, that converts it in a 0-10V range or 0-20mA range signal. Auxiliary power
supply allows to supply the output current loop. Moreover, the device is able to control two trip alarm relay outputs.
DAT 4235 IS has a 3 way isolation: input (connected to hazardous area devices) is 2000 Vac isolated from power supply and output (connected to safe area);
power supply and output are 1500 Vac isolated between them.
The “ DAT 4235 IS /A ” model converts the input signal in analogue output, the “ DAT 4235 IS /B ” model controls two output trip alarms. The “ DAT 4235 IS /C ”
model is able both to converts the input signal in analogue output and to control two output trip alarms.
Configuration and configuration is made by means of personal computer through the PRODAT-IS interface.
The device must be powered with a voltage between 20 and 30 Vdc; the “PWR” green led turned on indicate the correct power supply; the "THR1" and "THR2"
red led indicates the trip alarm status.
The device is housed in a rough self-extinguish plastic enclosure of 22.5 mm thickness suitable for DIN rail mounting.
DAT4235IS/A from Datexel comes with the following features:
- Protection mode: II (1) G [ Ex ia Ga ] IIC -- II (1) D [ Ex ia Da ] IIIC -- according to the Directive ATEX 2014/34/EU
- Tc, RTD, Res, mV, V, mA, Potentiometer configurable input
- 0 to 10V , 0 to 20mA configurable output
- PC configurable
- 2000 Vac galvanic isolation between input and output
- EMC compliance – CE mark
- Suitable for DIN rail mounting
Input type for Datexel DAT4235IS/A
Input for this model is as follows:
- Thermocouple: J, K, S, R, B, E, T, N
- RTD: Pt100, Pt1000, Ni100, Ni1000
- Voltage: mV, V
- Potentiometer
- Resistance, ohm, Kohm
Output type
Output for this temperature transmitter is:
- Direct Current: 4 mA … 20 mA
- Reverse Current: 20 mA … 4 mA
- Voltage: 0 ... 10
Power supply
power supply voltage for Datexel DAT4235IS/A is the standard 20 to 32 VDC. Also Reverse polarity protection is 60 VDC max.
Temperature & humidity Consideration
- Operative temperature -20°C ... +60°C
- Humidity (not condensed) 0 ... 90 %
Housing
- Material: Self-extinguish plastic
- Mounting: DIN Rail
- Weight: about 150 g.
Industries/applications
- Furnace
- Oil and gas
- Brick manufacturing
- Heat Exchangers
- Industrial Processes
- Heating/cooling systems
Series Information
Intrinsically safe smart series ATEX94/9/EC
The Intrinsically Safe SMART Series devices, type-approved according to Directive ATEX94/9/EC, are subdivided into three different product categories: universal input transmitters to be installed in a potentially explosive atmosphere (Zone 0) codes:
DAT 2015 IS, DAT 4035 IS, DAT 1010 IS, DAT 1015 IS, DAT 1065 IS.
Converters / Barriers for universal input or current loop (0-4…..20 mA), suitable for installation in safe zone for connections towards zone 0. codes:
DAT 4235 IS in the following versions:
A= Converter/Barrier, B= Double trip amplifier,
C= Converter/Barrier + Double trip amplifier.
DAT 5030 IS in the following versions:
A= Single-channel barrier, AH= HART transparent single-channel
barrier, B= Double-channel barrier, BH= HART transparent
double-channel barrier.
About Datexel:
Founded in 1992 from the commitment and aspiration of several partners as a small provincial company, through the years DATEXEL has become an established reality on Italian and international markets as a manufacturer of electronic equipment for industrial automation and control process.
The range of DATEXEL products includes: Transmitters, signal and temperature Converters (both analogue and digital), galvanic Isolators, signal Splitters, I/O Modules, Trip Amplifiers, Power Supply Units, current loop Isolators, analogue and digital Displays.
Documents
To View Data Sheet for Datexel Temperature Transmitter and Signal Converter DAT4235 IS/A Please Click HereAdditional Information
Input type: |
TC, RTD, voltage, potentiometer, resistance, current (details in datasheet) |
Input calibration: |
RTD > of ±0.1% fs or ±0.2°C. Res. Ohm > of ±0.1% fs or ±0.15 Ω. Res. KOhm > of ±0.2% fs or ±1 Ω. mV, Tc > of ±0.1% fs or ±10 uV V > of ±0.1% fs or ±2 mV. mA > of ±0.1% fs or ±6 uA |
Input impedance: |
TC, mV >= 10 M Ω. Volt >= 1 M Ω. Current ~ 50 Ω. |
Current: |
Min: 0mA. Max: 20mA. |
Voltage: |
Min: 0V. Max: 10V. |
Output calibration: |
Current ± 7 uA. Voltage ± 10 mV. |
Linearity: |
TC ± 0.2 % f.s. RTD ± 0.1 % f.s. |
Lead wire resistance influence: |
TC, mV <=0.8 uV/ Ω. RTD 3 wires 0.05%/ Ω (50 Ω balanced max.). RTD 4 wires 0.005%/ Ω (100 Ω balanced max.). |
Thermal Drift: |
Full-scale ± 0.01%/°C. CJC ± 0.01%/°C |
RTD excitation current: |
Typical 0.350 mA. |
CJC Comp.: |
± 0.5°C. |
Burnout values: |
Max. value about 23 mA or 10.8Vdc. Min. value 0 mA or 0Vdc. |
Response time (10÷ 90%): |
~0.4s. |
Trip alarms: |
Output type n° 2 SPDT Relays. Contact rating 2A , 250 Vac 2A , 30 Vdc. Load resistive. Minimum load 5Vdc, 10mA. Max Voltage 250 Vac (50/60 Hz) 110 Vdc. Isolation coil-to-contacts: 2000Vac, between contacts: 1000Vac. |
Power Supply: |
Supply Voltage 20 ÷ 30 Vdc. Polarity inverted protection 60 Vdc max. |
Isolation: |
Input/output 2000 Vac, 50 Hz, 1min. Input/Supply 2000 Vac, 50 Hz, 1min. Supply/Output 1500 Vac, 50 Hz, 1min. |
Temperature and humidity: |
Operating Temperature -20°C .. +60°C. Humidity (non-condensing) 0 .. 90 %. |
Housing: |
Material Self-extinguish plastic. Mounting DIN Rail Weight ~ 150 g. Dimensions (mm) : 120 x 100 x 22.5. |
EMC (for industrial environment): |
none |
Immunity: |
EN 61000-6-2. |
Emission: |
EN 61000-6-4. |